A station stands still without a fault: starved or blocked

A machine that stands still without a fault is usually waiting: for product from upstream (starved) or for space downstream (blocked). The cause is often two stations away. Use this page to trace a standstill along the line to its origin.

Page context

Line
Reference line RL-1: end-of-line packaging (RL-1)
Stations
Infeed and accumulation conveyor → Filler and capper → Labeller → Inspection and reject → Case packer → Palletiser and stretch wrapper
Lifecycle phase
Operation and maintenance
For
Operators, Maintenance technicians
Page type
Troubleshooting — Leads from a symptom to its cause and remedy
Line map of the reference line · RL-1
  1. Z1 · Filling

    1. Infeed and accumulation conveyorSystem integrator
    2. Filler and capperSupplier A
  2. Z2 · Labelling and inspection

    1. LabellerSupplier B
    2. Inspection and rejectSupplier B
  3. Z3 · Case packing

    1. Case packerSupplier C
  4. Z4 · Palletising

    1. Palletiser and stretch wrapperSupplier D

How to use this page

Find the symptom that matches what you see, then work through its causes from top to bottom — the most frequent cause comes first. “Check” tells you what to look at, “Remedy” what to do. Follow the line in the direction the page tells you: starved means look upstream, blocked means look downstream.

The case packer shows Suspended (starved), no fault

Where to look: Z3, look upstream towards Z2

  1. Possible cause 1

    Zone Z2 is stopped

    Check

    Line HMI: is “Zone stop Z2” or an open door shown?

    Remedy

    Restart Z2 as described in the restart procedure.

  2. Possible cause 2

    The labeller is Held, e.g. for a label reel change

    Check

    Labeller panel: reel empty or splice request?

    Remedy

    Change the reel following the labeller manual; the line continues on its own.

  3. Possible cause 3

    The inspection rejects every bottle

    Check

    Reject counter rising fast, reject bin filling

    Remedy

    Stop Z2 and check the label position and the camera image; see the inspection manual.

The labeller shows Suspended (blocked), no fault

Where to look: Z2, look downstream towards Z3 and Z4

  1. Possible cause 1

    The buffer ahead of the case packer is full

    Check

    HMI buffer display “buffer full” between Z2 and Z3

    Remedy

    Find why the case packer doesn’t take product — often the palletiser blocks it.

  2. Possible cause 2

    The palletiser waits for an empty pallet

    Check

    Palletiser panel: pallet magazine empty?

    Remedy

    Refill the pallet magazine; the palletiser restarts and the line follows.

  3. Possible cause 3

    The case packer has run out of cases

    Check

    Case packer panel: case magazine low or empty

    Remedy

    Refill the case magazine from outside the zone.

The whole line runs slower than rated, no station stops

Where to look: All zones

  1. Possible cause 1

    The line controller reduced the speed because a buffer is nearly full

    Check

    HMI trend of the buffer levels during the last 30 minutes

    Remedy

    Find the slowest station downstream of the full buffer and check its settings.

  2. Possible cause 2

    The filler runs at reduced speed after a product change

    Check

    Filler recipe: speed setpoint

    Remedy

    Load the correct recipe; ask the shift lead before changing setpoints.

If none of this helps

If the standstill returns more than three times per shift, or no cause in this list fits, call maintenance and note the times from the line history. Repeated micro-stops are a line issue, not a machine issue: they belong in the line’s downtime analysis, not in a single machine’s service call.