Glossary · PLC and control programming
Deterministic control
Also known as: Deterministic behavior, Deterministic execution
German: Deterministische Steuerung
In control engineering, deterministic control means that a controller produces the same outputs from the same inputs and state and reacts within a known worst-case time, so its behavior can be predicted and verified.
- PLC programming
- Functional safety
- OT security
In one sentence
Deterministic control means the same inputs give the same outputs within a known worst-case time – the basis for verifiable safety functions.
Example
A cyclic PLC task with a fixed 10 ms interval and a maximum jitter of 0.2 ms is deterministic; a PC application that answers "usually within 50 ms" is not.
How it applies
- Engineering: Determinism comes from cyclic or time-triggered tasks, a bounded program length, no unbounded loops or waits, and a network with guaranteed timing. It concerns both the logic (same result) and the timing (known worst case).
- Documentation: State which paths are deterministic and give their worst-case times; mark non-deterministic parts (HMI, cloud links, best-effort traffic) as outside the safety functions.
In risk assessment, PL analysis and security analysis
- Risk assessment (CE): A safety function can only be relied on when its behavior is predictable. Non-deterministic behavior has to be treated as a possible fault in the risk assessment.
- PL analysis: The response time in the safety requirements specification and the minimum distance under ISO 13855 need a worst case, which only a deterministic path provides. See Scan cycle and Real-time system.
- Security analysis: Non-deterministic paths (variable load, shared networks, background services) are where an attacker can add delay. Under IEC 62443 this is resource availability (FR 7); keep the deterministic paths separate and limit what may load them.
Naming this term in a document never shows conformity; the risk assessment, the validation of the safety functions and the security risk assessment do. EN 50742 is a CENELEC draft as of the review date: it is neither law nor a source of presumption of conformity.
Deterministic vs. fast
Fast means a short average reaction; deterministic means a known upper limit. A slow but deterministic controller can carry a safety function; a fast one with an unknown worst case cannot.