Glossary · Functional safety

Redundancy

Also known as: redundant design, multi-channel architecture

German: Redundanz

In functional safety, redundancy is the use of multiple independent channels or elements so that a single failure does not cause loss of the required function. It is effective only if the channels are sufficiently independent and faults are detected.

  • Functional safety
  • Systems engineering

In one sentence

Redundancy uses multiple independent channels so that one failure does not remove a required safety function.

Example

Two contactors in series switch off the motor of a conveyor; if one contact welds, the other still interrupts the power, and feedback monitoring reveals the welded contact.

How it applies

  • Functional safety: Redundancy is the basis of Categories 3 and 4 in ISO 13849-1 and of hardware fault tolerance in IEC 61508 and IEC 62061.
  • Integrated systems: Redundancy without detection only postpones failure. The first fault must be found by diagnostics or a test before a second fault occurs.
  • Evidence: Independence has to be shown, not assumed. The common-cause failure assessment is the evidence that the channels do not fail together.
  • Technical documentation: Wiring diagrams, spare part rules and maintenance steps must keep the channels separate. A shortcut during repair can reduce a two-channel design to one channel.

Redundancy vs. diversity

Redundancy provides more than one channel. Diversity makes those channels different, which also covers shared design flaws.

In risk assessment, PL analysis and security analysis

  • Risk assessment (CE): Redundancy is how a control system keeps a safety function after one fault. The risk assessment names the safety functions whose required PL or SIL makes a second channel necessary.
  • PL analysis: Category 3 and Category 4 of ISO 13849-1 are two-channel structures. Redundancy only counts together with diagnostic coverage (a fault in one channel must be detected) and with measures against common-cause failure (score of at least 65 points under Annex F).
  • Security analysis: Two channels that share a network, an engineering station or a firmware image share the attack path – an attack is a common cause that the CCF score does not cover. Assess redundant paths separately under IEC 62443 (zones and conduits, integrity of programs and firmware) and protect the access to both channels.

Naming this term in a document never shows conformity; the risk assessment, the validation of the safety functions and the security risk assessment do. EN 50742 is a CENELEC draft as of the review date: it is neither law nor a source of presumption of conformity.

By knowledge.aitechdoc.world · Published September 25, 2026 · Last reviewed

Source: IEC 61508:2010, Functional safety of electrical/electronic/programmable electronic safety-related systems

Definitions follow the cited standards and specifications. Where a source is a copyrighted publication, such as an ISO, IEC or EN standard, the definition is a close paraphrase, not a verbatim quotation, so as not to infringe copyright. We recommend reading the original publication. The sections “How it applies” are editorial commentary by AI TechDoc Knowledge and are not part of any standard.