Safety Integrity Level (SIL)

Also known as: SIL

German: Sicherheits-Integritätslevel (SIL)

In functional safety, a Safety Integrity Level (SIL) is a discrete level for specifying the safety integrity requirements of a safety function. IEC 61508 defines SIL 1 to SIL 4, and IEC 62061 uses SIL 1 to SIL 3 for machinery.

  • Functional safety
  • Verification

In one sentence

A Safety Integrity Level (SIL) specifies how much integrity a safety function needs: SIL 1 to 4 in IEC 61508, up to SIL 3 in IEC 62061.

Example

A safety-rated speed monitoring function on a CNC machine is specified as SIL 2 under IEC 62061, and the chosen drive and safety PLC carry certificates up to SIL 3.

How it applies

  • Functional safety: A SIL covers random hardware failures (quantified, for example as PFH) and systematic capability (development process, architecture constraints). Both must meet the level claimed.
  • Standards: IEC 61508 is generic and goes up to SIL 4. IEC 62061 applies it to machinery control systems up to SIL 3.
  • Technical documentation: State the SIL per safety function and name the standard. A component certificate "SIL 3 capable" only states what the component can support; the function needs its own verification.
  • Evidence: Keep the safety manual conditions of each component, such as proof test intervals, because the SIL claim depends on them.

SIL vs. Performance Level

SIL and PL are different scales from different standards. Their probability ranges overlap, which allows an approximate comparison, but the methods for determining them differ.

In risk assessment, PL analysis and security analysis

  • Risk assessment (CE): On machinery the required level of a safety function is usually stated as PLr (ISO 13849-1) or SIL (IEC 62061); both follow from the risk assessment, not from the controller's data sheet. A safety PLC rated "SIL 3 / PL e" only provides the capability for its own part.
  • PL analysis: The SIL of a subsystem limits what a safety function built from it can reach (SIL claim limit); the PL of the whole function is checked over all subsystems. See Safety integrity for the property itself.
  • Security analysis: IEC 61508 requires security threats to be analyzed when malevolent action is reasonably foreseeable, and refers to IEC 62443. A Security level is a different scale and never replaces or raises a SIL.

Naming this term in a document never shows conformity; the risk assessment, the validation of the safety functions and the security risk assessment do. EN 50742 is a CENELEC draft as of the review date: it is neither law nor a source of presumption of conformity.

By knowledge.aitechdoc.world · Published September 25, 2026 · Last reviewed

Source: IEC 61508:2010, Functional safety of electrical/electronic/programmable electronic safety-related systems

Definitions follow the cited standards and specifications. Where a source is a copyrighted publication, such as an ISO, IEC or EN standard, the definition is a close paraphrase, not a verbatim quotation, so as not to infringe copyright. We recommend reading the original publication. The sections “How it applies” are editorial commentary by AI TechDoc Knowledge and are not part of any standard.